Vigilon Compact Control

Vigilon Compact analogue addressable 1-2 loop panels offer small to medium sized building owners the unique system functionality of Vigilon with the very best in control panel aesthetics – stainless steel door options are available to provide a discreet and luxurious feel in upmarket office environments.

The introduction of innovative design features into this panel means that the wall space needed to mount the panel is now 60% smaller than a standard Vigilon installation.

Vigilon Compact analogue addressable panels fully comply with EN54: Parts 2 & 4 and can be specified with 1 or 2 detection loops, each capable of accommodating up to 200 Vigilon devices including repeat panels, interfaces, manual call points and S-Quad sensor/sounder/strobes.

Gent’s innovative new S-Quad is a combined multi-sensor range with speech, sounder and strobe in one intelligent unit.

Fully compatible with Gent’s S-Cubed alarm devices (offering sound, speech or strobe effects in combination), Vigilon Compact also offers the familiar advantages of combined sensor-sounders and loop powered beam detection with integral short circuit isolators fitted into every loop device.

Additional features

  • Vigilon’s powerful software allows the fire alarm system to be configured to meet the fire alarm needs of the building
  • Combining the proven reliability of the Vigilon range of sensors and true analogue sensing keeps false alarms to a minimum
  • Alarm sound levels can be increased by simply replacing a sensor with a sensor/sounder, saving costly additional wiring
  • To meet the requirements of BS 5839-1: 2002 the Vigilon Compact is supplied with separate zonal indication, visible at access level 1. This comprises 32 fire LEDs (secret till lit) which enables ‘at a glance’ overview indication, without the need for manual intervention by fire fighters

Dimensions (mm) w 338 h 403 d 101

TypeControl panel
Loop Capacity 200
Networking Capacity Upto 32 panels
Ingress Protection IP31
Approx Weight16.6 Kg (with batteries)
Operating Temperature 0oC to +45oC
Relevant Standards EN54 Pt 2 & 4
Batteries 2 x 12V @ 12 Ah
Battery Standby 24 Hours + 30 minutes alarm
Supply Voltage 216V – 253V 50Hz
Power Consumption 140 W
Cable Entry Top and rear knockins
Auxiliary Contacts Programmable to activate on Fire, Fault or Disablement. (1 x SPCO 1 x DPCO)
Sounder Circuits 2 circuits @ 250mA each
Monitored input 1 input which is programmable to perform a logical action via a command build
Communication ports2 x RS485, 1 x RS232 selectable functions